Ross Hill 0302-1508-00 Motor Circuit Protector, TEC36015WL
The 15 A value is continuous amperes; 42 through 198 A are instantaneous magnetic pickup positions, not alternate device ratings.
Ross Hill 0302-1508-00 identifies the three-pole TEC36015WL magnetic-only motor circuit protector. ABB publishes the core catalog number TEC36015 at 15 continuous amperes with seven magnetic pickup positions: 42, 68, 94, 120, 146, 172, and 198 A. Keep the full WL suffix from the installed identification when requesting a replacement.
Independent supplier. Edmundson Industrial is not appointed, endorsed, or sponsored by Ross Hill, NOV, GE, ABB, Mersen, or any other manufacturer named on this page. Names and part numbers appear for identification only. Availability, condition, price, and lead time are confirmed for each request.
| RHCC part number | 0302-1508-00 |
|---|---|
| Full equipment reference | TEC36015WL |
| ABB trip-table catalog number | TEC36015 |
| Device | Three-pole magnetic-only motor circuit protector |
| Continuous amperes | 15 A |
| Magnetic pickup positions | 42, 68, 94, 120, 146, 172, and 198 A |
| Pickup function | Instantaneous high-current response |
| Overload boundary | Motor overload protection remains a separate coordinated function |
| Suffix boundary | Preserve WL from the complete installed reference |
Part-number identification
Use TEC36015WL as the complete equipment reference. ABB trip tables establish the TEC36015 continuous-current and pickup data. The motor, overload relay, heaters, selected dial position, starter, and circuit fault duty complete the protection application.
The complete installed label remains the ordering reference. Match the part number, electrical ratings, physical interface, and circuit duty before approving a replacement.
Continuous amperes and pickup amperes are different
15 A is the continuous-current catalog value. The 42 to 198 A values are instantaneous magnetic pickup settings. They define where the protector responds to high current and do not turn the device into a breaker with seven continuous ratings.
Set magnetic pickup from motor starting behavior
ABB recommends placing magnetic pickup just above the motor starting inrush, using the next higher position that carries the start. Record the existing dial position and measured starting behavior before adjustment; protection settings belong to the equipment coordination review.
The 15 A device has a 42 to 198 A magnetic range
The low pickup position is 42 A and the high position is 198 A, with five documented positions between them. Select the setting from the motor-start and coordination requirements, not from the continuous 15 A value alone.
Motor overload protection remains separate
A magnetic-only protector does not replace the starter overload relay and correctly selected heater elements. Provide both sides of the protection scheme so fault response, motor overload protection, conductor protection, and starter withstand remain coordinated.
Also searched as
0302-1508-00 · 0302150800 · TEC36015WL · TEC36015 · TEC 15 amp magnetic breaker · GE motor circuit protector 15 A
What to send with your request
Separate the continuous-current identity, selected magnetic pickup, and overload system.
- Complete RHCC and TEC numbers, including WL
- Photographs of the nameplate, pickup dial, lugs, mounting, and complete bucket
- Existing pickup position and documented motor-starting current
- Motor voltage, phase, horsepower, full-load current, and service factor
- Starter, overload relay, heater numbers, and upstream protection
- Circuit fault-duty information, quantity required, and need-by date
A purchase order is not required for an identification review. Send the complete numbers and clear equipment photographs so the quoted item can be checked against the application.
Related
Identification checkpoint
For RHCC 0302-1508-00, confirm continuous amperes: 15 A; pickup function: Instantaneous high-current response; full equipment reference: TEC36015WL. Use the installed label and complete suffix before treating another item as equivalent.
Distinguish the 15 A motor circuit protector
RHCC 0302-1508-00 is the TEC36015WL record, with 15 A continuous current and published magnetic pickup positions from 42 through 198 A. The related TEC36050WL record is 50 A with a different pickup range. Match the complete reference and preserve the WL suffix before approving the device.
FAQ
What is Ross Hill 0302-1508-00?
What is the continuous-current value of TEC36015?
What magnetic pickup positions are published for TEC36015?
Are the pickup values alternate continuous ratings?
Does this device provide motor overload protection?
Availability & Quote
Want a quick quote for 0302-1508-00?
Fill out your contact info here, and we'll get a quote sent to you ASAP!