EDMUNDSON INDUSTRIALOILFIELD ELECTRICAL SUPPLY
Drilling Rig Electrical · 50 A magnetic motor protection

Ross Hill 0302-1501-00 Motor Circuit Protector, TEC36050WL

The 50 A value is continuous amperes; 180 through 660 A are instantaneous magnetic pickup positions, not alternate device ratings.

Ross Hill 0302-1501-00 identifies the three-pole TEC36050WL magnetic-only motor circuit protector. ABB publishes the core catalog number TEC36050 at 50 continuous amperes with seven magnetic pickup positions: 180, 260, 340, 420, 500, 580, and 660 A. Keep the full WL suffix from the installed identification when requesting a replacement.

Independent supplier. Edmundson Industrial is not appointed, endorsed, or sponsored by Ross Hill, NOV, GE, ABB, Mersen, or any other manufacturer named on this page. Names and part numbers appear for identification only. Availability, condition, price, and lead time are confirmed for each request.

Identification details for Ross Hill 0302-1501-00
RHCC part number0302-1501-00
Full equipment referenceTEC36050WL
ABB trip-table catalog numberTEC36050
DeviceThree-pole magnetic-only motor circuit protector
Continuous amperes50 A
Magnetic pickup positions180, 260, 340, 420, 500, 580, and 660 A
Pickup functionInstantaneous high-current response
Overload boundaryMotor overload protection remains a separate coordinated function
Suffix boundaryPreserve WL from the complete installed reference

Part-number identification

Use TEC36050WL as the complete equipment reference. ABB trip tables establish the TEC36050 continuous-current and pickup data. The motor, overload relay, heaters, selected dial position, starter, and circuit fault duty complete the protection application.

The complete installed label remains the ordering reference. Match the part number, electrical ratings, physical interface, and circuit duty before approving a replacement.

Continuous amperes and pickup amperes are different

50 A is the continuous-current catalog value. The 180 to 660 A values are instantaneous magnetic pickup settings. They define where the protector responds to high current and do not turn the device into a breaker with seven continuous ratings.

Set magnetic pickup from motor starting behavior

ABB recommends placing magnetic pickup just above the motor starting inrush, using the next higher position that carries the start. Record the existing dial position and measured starting behavior before adjustment; protection settings belong to the equipment coordination review.

The 50 A frame uses a 180 to 660 A magnetic pickup range

The pickup dial starts at 180 A and ends at 660 A. Those values address high-current response during starting and fault conditions. Confirm motor inrush and the complete protection study before changing the established dial position.

Motor overload protection remains separate

A magnetic-only protector does not replace the starter overload relay and correctly selected heater elements. Provide both sides of the protection scheme so fault response, motor overload protection, conductor protection, and starter withstand remain coordinated.

Also searched as

0302-1501-00 · 0302150100 · TEC36050WL · TEC36050 · TEC 50 amp magnetic breaker · GE motor circuit protector 50 A

What to send with your request

Separate the continuous-current identity, selected magnetic pickup, and overload system.

  • Complete RHCC and TEC numbers, including WL
  • Photographs of the nameplate, pickup dial, lugs, mounting, and complete bucket
  • Existing pickup position and documented motor-starting current
  • Motor voltage, phase, horsepower, full-load current, and service factor
  • Starter, overload relay, heater numbers, and upstream protection
  • Circuit fault-duty information, quantity required, and need-by date

A purchase order is not required for an identification review. Send the complete numbers and clear equipment photographs so the quoted item can be checked against the application.

Related

Identification checkpoint

For RHCC 0302-1501-00, confirm continuous amperes: 50 A; pickup function: Instantaneous high-current response; full equipment reference: TEC36050WL. Use the installed label and complete suffix before treating another item as equivalent.

Distinguish the 50 A motor circuit protector

RHCC 0302-1501-00 is the TEC36050WL record, with 50 A continuous current and published magnetic pickup positions from 180 through 660 A. The related TEC36015WL record is 15 A with a different pickup range. Preserve the complete WL suffix and coordinate overload protection separately.

FAQ

What is Ross Hill 0302-1501-00?
It identifies the three-pole TEC36050WL magnetic-only motor circuit protector.
What is the continuous-current value of TEC36050?
ABB publishes 50 continuous amperes.
What magnetic pickup positions are published for TEC36050?
The seven positions are 180, 260, 340, 420, 500, 580, and 660 A.
Are the pickup values alternate continuous ratings?
No. They are instantaneous magnetic pickup settings; the cataloged continuous-current value remains separate.
Does this device provide motor overload protection?
Motor overload protection remains a separate coordinated function using the starter overload relay and correctly selected heaters.