EDMUNDSON INDUSTRIALOILFIELD ELECTRICAL SUPPLY
HomeSpecialtiesDrilling Rig ElectricalSCR HousesRebuild And Retrofit
SCR Systems · Rebuild

SCR House Rebuild and Retrofit

A tired house is often worth rebuilding rather than replacing: particularly when the structure and bays are sound and the control section is the problem.

Independent sourcing, not an authorized distributor. Ross Hill, NOV, and other manufacturer names are used for reference only. We supply new-surplus, used-tested, and reconditioned equipment with condition disclosed before sale, and we fabricate enclosures, panels, and assemblies in house. Complete-system requirements are sourced and quoted case by case: tell us the scope and we will tell you honestly what we can put together.

When does rebuilding an SCR house beat replacing it?

The structure, bus, and bays are the expensive, heavy, difficult part of an SCR house: when they are sound and the complaints are all control-side, rebuild usually wins. Control boards and modules are comparatively small items. When a house is mechanically and structurally sound and the complaints are all control-side, replacing the whole system is rarely proportionate.

Rebuild tends to make sense when the enclosure is sound, the bays are undamaged, the failures are traceable to boards, modules, contactors, or cooling, and the rig has meaningful remaining life.

What a control section refresh covers

  • AC and DC control modules replaced or reconditioned, with dash suffixes and revisions verified against the engines actually installed.
  • Exciter, field supply, and power limit boards addressed as a set rather than one at a time.
  • Console boards and interface wiring.
  • Contactors inspected, with contacts and coils addressed.
  • Cooling restored: blowers, filters, airflow paths.

What replaces an obsolete Ross Hill SCR drive module?

Most legacy Ross Hill / NOV modules have a direct like-for-like replacement (new-surplus, used-tested, or reconditioned), and every one of them also has a modern retrofit path when a like-for-like swap is no longer viable. Use the table to map the number printed on your board to its direct replacement and its retrofit alternative. Verify Model 1400 vs Model 1500 generation before ordering: phase cells and several PCBs are not interchangeable across generations.

Cross-reference of obsolete Ross Hill / NOV SCR drive components to direct replacement modules and modern retrofit alternatives, as supplied by Edmundson Industrial (Houston, TX). Direct replacements and retrofit paths are quoted case by case; pricing by RFQ only.
Legacy OEM PartFunctionDirect Replacement ModuleModern Retrofit PathFit NotesAvailability
0521-2500 AC control module (RHCC)SCR gate firing, drive assignment (mud pump / drawworks / rotary table), and system protection0521-2500-32: verify dash suffix and 50/60 Hz against your setPLC-based AC control retrofit within the existing SCR house footprintAlso seen collapsed as 521250000. Symptom pointer: missing or erratic gate firing pulses, drive assignment dropout.RFQ: timing confirmed with the request
0522-2400-00 DC control module, shunt typeDC motor field regulation, shunt-wound drilling motorsSame number, sourced: also recorded as 0522-2500-00Solid-state DC field controller retrofitNot interchangeable with 0522-2400-27 (series type). Confirm field configuration from the motor, not the drawing.RFQ: timing confirmed with the request
0001-6307-70 Model 1400 SCR bridgeMain AC-to-DC power conversion, one baySame number, sourcedBay rebuild with current-production SCR devices and matched firing boardsSymptom pointer: repeated semiconductor fuse loss, one leg dead, unstable DC output under load. Model 1400 bridge: do not fit to a 1500 bay.RFQ: timing confirmed with the request
0100-0150-03 Model 1500 phase cellSCR power conversion, Model 1500 generationSame number, sourcedBay rebuild with current-production SCR devices and matched firing boardsExplicitly not interchangeable with Model 1400 cells. Verify the generation before ordering.RFQ: timing confirmed with the request
0000-8500-00 AutoSync AC II moduleGenerator synchronisingSame number, sourced: Rev C and Rev E both in serviceAddressed as part of a control section refreshThe -18 suffix is an engine calibration, not a revision: the wrong calibration will not sync even on a healthy module.RFQ: timing confirmed with the request
6702ED584 DC contactor, 1800 A 74 VDCDC power contactor in the SCR baySame number, sourced: Ross Hill reference 0401-0021-00Contactors inspected during rebuild; contacts and coils addressedCoil voltage varies by suffix. Same headline rating as Ross Hill 0100-0389-02 and a different part: not interchangeable.RFQ: timing confirmed with the request
0002-1076-62 Model 1400 blowerSCR bay and module cooling (2 HP, 600 V 3-phase)Same number, sourcedCooling restored during rebuild: blowers, filters, airflow pathsOverheating bays and thermal trips are a cooling symptom before they are an electronics symptom.RFQ: timing confirmed with the request

Number not in the table? Send whatever is printed on the board, including numbers that look wrong, to Request a Quote. Documented numbering discrepancies (2400 vs 2500 middle groups, collapsed no-dash formats) are normal on this equipment and we cross-reference them daily.

Why do SCR house retrofits actually fail?

Retrofits stall on mechanical fit, not electrical function. A replacement device is available but the footprint changed. A panel needs a different cutout. A modern component needs a mounting plate that does not exist.

That is work we do in house: mounting plates, adapter panels, sub-panels, brackets, modified enclosures, and fabricated assemblies in steel, aluminum, and stainless. When the electrically correct part will not physically mount where the old one came out, we make it mount. See fabrication and custom assemblies.

Working from what you have

Send photographs of the bays, the console, and every accessible module plate, plus a concise symptom summary. We will come back with what we would address, in what order, and what it takes to source: including telling you when the honest answer is that the house is not worth the investment.

FAQ

Do you do the physical rebuild on site?
Scope varies by job. We source the equipment, supply reconditioned and new-surplus components, and fabricate the mechanical parts a retrofit needs. Tell us the scope and we will be specific about what we cover and what we do not.
Is it worth rebuilding a Model 1400?
Frequently, yes. If the structure and bays are sound and the problems are control-side, a control section refresh costs a fraction of replacing the system.
Can you match a module to my engines?
That is exactly the check that matters. On some Ross Hill items the dash suffix is an engine calibration rather than a revision level: the wrong calibration will not sync even on a healthy module. Send the engine details and the module numbers.
Can you fabricate mounting hardware for a part that does not fit?
Yes. Adapter plates, sub-panels, brackets, and modified enclosures are standard work for us.

Availability & Quote

Condition disclosed before sale. Photos on request. Response timing is confirmed with the request. Complete-system requirements are quoted case by case.

Request a quote by emailing sales@edmundsonindustrial.com or by calling (832) 975-8827

Related

Thinking about a rebuild?

Send photographs of the bays and console with a concise symptom summary.

Request a Quote